UVS SERIES OF UV REACTORS
Different Applications Require Different Doses of UV:

The UV dose required is a function of the desired effluent quality relative to the incoming water quality and UV Transmittance (UVT).

Following are typical dose levels for common UV purification applications:

Application Typical Dose Required
Disinfection 30 mJ/cm2 (30,000 µW×sec/cm2)
Ozone Destruction 90 mJ/cm2 (254 nm only)
TOC Reduction 120 mJ/cm2 to 360 mJ/cm2
Chlorine/Chloramine Removal 100 mJ/cm2 to 900 mJ/cm2

UVS Series Specifications
Model Number:
UVS219T - 30
UVS222S - 35
UVS228S - 50
UVS238S - 65
Flow rate for Disinfection (30 mJ/cm2 @ 99% UVT ):
30 gpm
6.8m3/hr
35 gpm
8m3/hr
50 gpm
11m3/hr
65 gpm
15m3/hr
Flow rate for TOC Reduction (300 mJ/cm2 @ 99% UVT ):
3.0 gpm
0.68m3/hr
3.5 gpm
0.79m3/hr
5.0 gpm
1.14m3/hr
6.5 gpm
1.48m3/hr
Number of Lamps
1
1
1
1
UV Chamber dimensions
L × W × H inches (mm)
22" × 6" × 7"
(559 × 152 × 178)
24" × 6" × 7"
(610 × 152 × 178)
30" × 6" × 7"
(782 × 152 × 178)
40" × 6" × 7"
(1016 × 152 × 178)
Control Panel size
L × D × H inches (mm)
8" × 6" × 10"
(203 × 152 × 254)
8" × 6" × 10"
(203 × 152 × 254)
8" × 6" × 10"
(203 × 152 × 254)
8" × 6" × 10"
(203 × 152 × 254)
Total Operating Power
85 Watts
85 Watts
100 Watts
125 Watts
Electrical Requirements
1 amps @ 120V
0.5 amps @ 220V
1 amps @ 120V
0.5 amps @ 220V
1 amps @ 120V
0.5 amps @ 220V
1.2 amps @ 120V
0.7 amps @ 220V
Inlet/Outlet
(Size and Type)
3/4" Swagelok
1 1/2" Sanitary Flange
1 1/2" Sanitary Flange
1 1/2" Sanitary Flange
Adapters are available for virtually and size and type of connection (sanitary flange, NPT, and 150# bolthole flange)
Dose required may vary depending on water quality factors. 1 mJ/cm2 = 1000 µW×sec/cm2. Specifications subject to change without notice.
Size of UVS228S-50 versus Competitive system for 50 gpm Disinfection applications.
All systems from UV Sciences include the following as standard:
  • Water contact surfaces 316 L Stainless Steel, Quartz, and Viton.
  • High intensity low pressure amalgam lamp for maximum output.
  • Electronic ballast for maximum lamp effectiveness.
  • NIST traceable UV intensity monitor and alarm.
  • Alarms, LED indicators and dual hour meters.
  • Easy - change lamp connectors (no tools required).
  • NEMA 4X control unit
  • 4 - 20 mA signal interface for remote monitoring and control capability.
  • Controls and components meet UL and CE regulatory requirements.
  • Operating pressure up to 150 p.s.i. at 32° - 140° F (0° - 60° C).

Innovation Drives Performance for the UVS Series
Model Number:
UVS322S - 100
UVS328S - 150
UVS338S - 225
UVS428S - 300
UVS438S - 500
Flow Rate for Disinfection (99% UVT ):
100 gpm
23m3/hr
150 gpm
34m3/hr
225 gpm
50m3/hr
300 gpm
68m3/hr
500 gpm
112m3/hr
Flow Rate for Disinfection (95% UVT ):
65 gpm
15m3/hr
100 gpm
23m3/hr
150 gpm
34m3/hr
200 gpm
45m3/hr
333 gpm
75m3/hr
Number of Lamps
1
1
1
2
2
Lamp Length
inches (mm)
22"
(711 mm)
28"
(711 mm)
38"
(914 mm)
28"
(711 mm)
38"
(914 mm)
Reactor Chamber Size
L × W × H inches (mm)
24" × 6" × 10"
(610 × 152 × 254)
30" × 6" × 10"
(762 × 152 × 254)
40" × 6" × 10"
(1016 × 152 × 254)
30" × 8" × 12"
(762 × 203 × 305)
40" × 8" × 12"
(1016 × 203 × 305)
Control Panel size
L × D × H inches (mm)
8" × 6" × 10"
(203 × 152 × 254)
8" × 6" × 10"
(203 × 152 × 254)
8" × 6" × 10"
(203 × 152 × 254)
8" × 6" × 10"
(203 × 152 × 254)
8" × 6" × 10"
(203 × 152 × 254)
Total Operating Power
100 Watts
100 Watts
125 Watts
160 Watts
200 Watts
Electrical Requirements
1 amps @ 120V
0.5 amps @ 220V
1 amps @ 120V
0.5 amps @ 220V
1.2 amps @ 120V
0.6 amps @ 220V
1.4 amps @ 120V
0.7 amps @ 220V
1.7 amps @ 120V
0.9 amps @ 220V
Inlet/Outlet Size
(sanitary flange standard)
2"
2"
2"
3"
3"
Adapters are available for virtually and size and type of connection (sanitary flange, NPT, and 150# bolthole flange)
Max Operating Pressure
150 p.s.i. (10 bar)
150 p.s.i. (10 bar)
150 p.s.i. (10 bar)
150 p.s.i. (10 bar)
150 p.s.i. (10 bar)
Operating Temperature Range
3° - 40° C
36° - 104° F
3° - 40° C
36° - 104° F
3° - 40° C
36° - 104° F
3° - 40° C
36° - 104° F
3° - 40° C
36° - 104° F
UV Intensity Monitor
(NIST Traceable)
Standard
Standard
Standard
Standard
Standard
UV Intensity Monitor provides realtime validation of UV dose and is strongly recommended for any UV system.
Stainless Steel Control Box
Rated: NEMA 4 and IP 65
Standard
Standard
Standard
Standard
Standard
20 mA Signal for Remote Monitoring and Control
Standard
Standard
Standard
Standard
Standard
Alarms and LED Indictors for Operating Status
Standard
Standard
Standard
Standard
Standard
* Based on 30 mJ/cm2or 30,000 µW×sec/cm2 (1 mJ/cm2 = 1000 µW×sec/cm2) Specifications subject to change without notice.
Relative Size Comparison of UVS328S-150 versus Competitive System
(both systems using Amalgam lamps):

 

 
HOME  |  SOLUTIONS  |  SERVICE & PARTS   |  CONTRACT  |  ABOUT UV   |  ABOUT US   |  CONTACT US
SURFACE CURING  |  SPOT CURING  |  AIR DISINFECTION  |  MUNICIPALITY  |  LAMP PROTECTION
 
© 2006 Radiant Industrial Solutions. All rights reserved